Power Factor Calculator

Fill in any two of active power, reactive power, apparent power and power factor. The calculator works out the others, and then the capacitor power and the capacitance per capacitor needed to reach the target power factor.

Free Runs in your browser Checked Tuesday, November 10, 2026

The real power the load uses, in kilowatts. Fill in any two of P, Q, S and cos φ, and leave the other two empty.

The reactive power of the load, in kvar.

The apparent power, in kVA: the current times the voltage.

Between 0 and 1: the ratio of P to S. Type 0.85 for 0.85.

The power factor the correction should reach, for example 0.95.

Supply

A single-phase or a three-phase network.

Capacitor connection

Delta: each capacitor sits across a full line voltage. Star: each sits across the line voltage divided by √3.

Single-phase: the voltage across the capacitor. Three-phase: the line-to-line voltage.

50 Hz in most countries, 60 Hz in North America.

Result

Capacitor power to add (kvar) — The reactive power the capacitor bank must supply to reach the target.
Capacitance per capacitor (µF) — The value of each capacitor in the bank, in microfarads.
Active power P (kW) —
Reactive power Q (kvar) —
Apparent power S (kVA) —
Power factor cos φ —
Phase angle φ (degrees) —

Working, step by step

This tool runs in your browser. What you enter is not sent to us.

How to use it

  1. Type any two of Active power P, Reactive power Q, Apparent power S and Power factor cos φ, and leave the other two empty. The calculator fills in the rest.
  2. Type the Target power factor, for example 0.95, and choose the Supply: single-phase or three-phase.
  3. For three-phase, choose how the capacitors are wired, then type the Voltage and the Frequency of the network.
  4. Read Capacitor power to add and the Capacitance per capacitor; the working is in Working, step by step.

The power triangle

A load with a power factor below 1 draws more current than its useful work needs. Its apparent power S is the vector sum of the active power P, which does the work, and the reactive power Q, which the source and the load exchange every cycle.

S = √(P² + Q²)
cos φ = P ÷ S
Q = P × tan φ = S × sin φ

P  active power (kW)     Q  reactive power (kvar)     S  apparent power (kVA)
  • An inductive (lagging) load, such as an induction motor, has a positive Q. A capacitor supplies that Q, so the source carries less current.
  • The power factor is P ÷ S: at 1 all the current does useful work.

Sizing the capacitor

To raise the power factor from cos φ1 to cos φ2, the bank must supply Qc = P × (tan φ1 − tan φ2). A capacitor of reactance X supplies Q = V² ÷ X, and X = 1 ÷ (2πfC), so the capacitance follows from the reactive power.

Qc = P × (tan φ1 − tan φ2)

Single-phase, or star with V the line voltage:  C = Qc ÷ (2πfV²)
Three-phase delta, V the line voltage:          C = Qc ÷ (3 × 2πfV²)

C capacitance of one capacitor (F)   f frequency (Hz)   V voltage across it (V)
  • In delta each capacitor works across a full line voltage. For the same total kvar it is one third of the capacitance of a star-connected capacitor.

What the calculator does not cover

  • Harmonics, and the resonance a capacitor can form with the supply. Some networks need a detuned or filtered bank.
  • Leading (capacitive) loads, where Q has a negative sign. The calculator assumes the usual lagging load.
  • Voltage rise, switching and protection of the bank. Check them against the rules of your network operator and of the capacitor maker.

Worked example: 80 kW at cos φ 0.7, corrected to 0.95 with a 400 V delta bank

The apparent power is S = 80 ÷ 0.7 = 114.29 kVA, and the reactive power is Q = 80 × tan(arccos 0.7) = 81.62 kvar. The phase angle is 45.57°.

To correct to 0.95, tan φ1 = 1.020 and tan φ2 = 0.329, so Qc = 80 × (1.020 − 0.329) = 55.32 kvar.

For a delta bank at 400 V and 50 Hz, C = 55,320 var ÷ (3 × 2π × 50 × 400²) = 366.9 µF for each of the three capacitors. In star at the same voltage each would need 1,101 µF.

Frequently asked questions

What is a power factor?

The power factor is cos φ, the ratio of active power to apparent power. A value of 1 means all the current does useful work. Inductive loads such as motors have a lower power factor, so they draw more current for the same useful power.

Why does correcting the power factor reduce the current?

The current is the apparent power divided by the voltage. Correction lowers the reactive part of that current while the active power stays the same, so cables and transformers carry less current for the same work.

Why does a delta bank need smaller capacitors?

In delta each capacitor sees the full line voltage, so it supplies more reactive power per microfarad. In star it sees the line voltage divided by √3, so each capacitor has to be three times larger for the same total kvar.

What if my power factor is already above the target?

The calculator then shows zero kvar and no capacitance, because the load already meets the target and needs no capacitor.

Can I enter the powers in watts or volt-amperes?

The boxes take kilowatts, kilovolt-amperes and kilovars. Type 80 for 80 kW, not 80,000 W.