Reynolds Number Calculator

Type the temperature of the water, its flow in litres per second and the inside diameter of the pipe. The page gives the Reynolds number and whether the flow is laminar, transitional or turbulent.

Free Runs in your browser Checked Wednesday, November 11, 2026

The temperature of the water, from 0 to 100 °C. Water at this temperature is liquid at its own saturation pressure.

The water flow through the pipe, in litres per second. One litre per second is 0.001 cubic metres per second.

The inside diameter of the pipe, not the outside one, in millimetres. A 150 mm water main is typed as 150.

Result

Reynolds number — The ratio of inertia to viscous forces in the flow. It has no unit.
Flow regime — The regime of pipe flow for this number, by the bands of the EPANET manual.
Mean velocity, m/s — The average speed of the water across the pipe.
Dynamic viscosity, mPa·s — How thick the water is, at this temperature. Water at 20 °C is about 1 mPa·s.
Density, kg/m³ — The mass of a cubic metre of water at this temperature.

How the figures are worked out

This tool runs in your browser. What you enter is not sent to us.

How to use it

  1. Type the Water temperature, °C, for example 20.
  2. Type the Flow rate, L/s and the Inside diameter, mm of the pipe, for example 20 and 150.
  3. Read the Reynolds number and the Flow regime, then the velocity, the viscosity and the steps.

How the Reynolds number is calculated

The Reynolds number compares the inertia of a flowing fluid with its viscous friction. For water in a full round pipe it is the density times the mean velocity times the diameter, divided by the viscosity.

Re = ρ × v × D ÷ μ
v  = Q ÷ (π × D² ÷ 4)

Re = Reynolds number, no unit
ρ  = density of the water, kg/m³
v  = mean velocity in the pipe, m/s
D  = inside diameter, m
μ  = dynamic viscosity, Pa·s
Q  = flow, m³/s
  • The number grows with the speed, the pipe size and the density, and falls as the viscosity rises.
  • Warm water is less viscous than cold water. At 100 °C its viscosity is about 28 % of its value at 20 °C, so the same flow in the same pipe gives a Reynolds number about 3.4 times as large.
  • The density and the viscosity come from the IAPWS equations for water at its saturation pressure, so the figures follow the water as its temperature changes.

Flow regimes in a pipe

The EPANET manual gives the bands of pipe flow: the Hagen-Poiseuille formula applies to laminar flow below a Reynolds number of 2,000, the flow is transitional from 2,000 to 4,000, and it is fully turbulent above 4,000.

Reynolds number Flow regime
Below 2,000 Laminar
2,000 to 4,000 Transitional
Above 4,000 Turbulent

What the calculator does not include

  • Liquids other than water, and gases. Their density and viscosity are different, and they need their own values.
  • Water above 100 °C in a pressurised pipe, where the pressure changes the properties. The page uses the water at its own saturation pressure.
  • Ducts that are not round, which need a hydraulic diameter, and open channels with a free surface.

Worked example: 20 L/s in a 150 mm pipe at 20 °C

At 20 °C water has a density of 998.16 kg/m³ and a viscosity of 1.0016 mPa·s. The flow of 0.020 m³/s in a pipe of 0.150 m inside diameter has a flow area of 0.0176715 m², so the mean velocity is 1.1318 m/s. The Reynolds number is 998.16 × 1.1318 × 0.150 ÷ 0.00100163 = 169,178, far above 4,000, so the flow is turbulent. The steps show rounded figures; the page computes with the full values.

Figure Value
Reynolds number 169,178
Flow regime Turbulent (above 4,000)
Mean velocity 1.132 m/s
Dynamic viscosity 1.0016 mPa·s

Frequently asked questions

At which Reynolds number does the flow in a pipe become turbulent?

The EPANET manual ends laminar flow at 2,000 and calls the flow fully turbulent above 4,000. Between the two the flow is transitional, and its behaviour is less predictable.

Why does warm water give a higher Reynolds number?

Its viscosity is lower, so the same flow in the same pipe gives a larger number. At 100 °C the viscosity is about 28 % of its value at 20 °C, and the Reynolds number is about 3.4 times as large.

Does a higher velocity always mean a higher Reynolds number?

Yes, for the same pipe and fluid, because the number is proportional to the velocity. The pipe size and the fluid matter too, so two pipes with the same speed can have very different numbers.

Can I use the calculator for oil or air?

No. The density and viscosity are those of water at its saturation pressure. Oil, air and other fluids need their own density and viscosity values.

Is my data sent to a server?

No. The calculation runs in your browser, and nothing you type is sent to us or stored.

Sources

Figures and text last checked on Wednesday, November 11, 2026.